Description
Benelec 176905 – Replacement Gas Capsule UC800 V
Suitable for 176210 EMP
Replaceable Gas Capsules
Part# Breakdown Voltage (V)
176901 90
176902 230
176903 350
176904 600
176905 800
176906 1000
Features
Fast response time
Suitable for direct strikes
Stable performance over life
Very low capacitance
High insulation resistance
Test Environment (@ 25°C)
Parameter Min Typ Max Unit
DC Breakdown Voltage 72 90 108V
184 230 276
280 350 420
480 600 720
640 800 960
800 1000 1200
Insulation Resistance 1*109 – – Ω
Capacitance – – 1.5 pF
Climatic Category IEC60068-1 40/90/21
Operational Temperature -40 – +125 °C
Applications
Communication lines
CATV equipment
Test equipment
Data lines, power supply
Base Station
Approva Medical electronics ls
UL recognised: File Number E32624B
Meets RoHS
ITU Rec K12
GB9043
The 17690X series replaceable Gas Capsules are designed
for a high degree of surge protection. It operates on the
gas physical principle of the highly effective arc
discharge. The 17690X series is used for protecting
equipment for which higher voltage limits and holdover
voltage are necessary. These gas capsules are for use with
the Benelec 176210 Lightning Arrestor. 176210
Lightning Arrestor
Specifications
Parameter
Part Number
Unit
176901 176902 176903 176904 176905 176906
DC Breakdown Voltage (1)
72 ~ 108 195 ~ 265 297 ~ 403 480 ~ 720 640 ~ 960 800 ~ 1200 V
80 ~ 120 %
Impulse Breakdown Voltage (2) ≤600 ≤700 ≤1000 ≤1400 ≤1450 ≤1500 V
Insulation Resistance (3) ≥1*109 Ω
Nominal AC Discharge Current (4) 20 A
Nom. Impulse Discharge Current (5)
10 shots 8/20µs
1 shot 8/20µs
1 shot 10/350µs
300 shots 10/1000µs
1500 shots 10/1000µs
20kA
25
4
200
A
10
Arc Voltage @ 1A -15 V
Holdover Voltage 52 80 135 V
Weight ≤1.5 g
Remarks:
(1) At 100 V/s
(2) At 1kV/µs
(3) Except for 90V types measured at 50 VDC, other types are measured at 100 VDC
(4) 50 Hz, 1s, 10 shots
(5) For each test new gas discharge tube shall be used.
Performance Characteristics